Arkansas Journeyman Plumber Calculations Practice

Each problem shows the formula, the numbers and every step. The app generates new problems without limit.
Question 1
Calculation
Use 0.433 psi per foot of water. What pressure does a 10-ft head of water put on the lowest joint of a section under test?
Question 2
Calculation
A shower measures 30 inches by 32 inches inside. Use the IPC minimums: 900 sq in of area and 30 inches as the smallest dimension. Does the shower comply?
Question 3
Calculation
Use 0.433 psi per foot of elevation. The static pressure at the street meter is 65 psi. What is the static pressure at a fixture 35 ft above the meter?
Question 4
Calculation
A 40-ft horizontal drain is laid at 1/4 inch per foot. How much total fall does it have?
Question 5
Calculation
A 1-1/2-inch fixture drain slopes at 1/4 inch per foot. Use the IPC rule that the fall from trap weir to vent may not exceed one pipe diameter. What is the longest run before the vent opening would drop below the weir?
Question 6
Calculation
Use 8.33 lb per gallon and 1 Btu per lb per °F. How many Btu are needed to raise 40 gallons of water from 50°F to 120°F?
Question 7
Calculation
Use 1,000 Btu per cubic foot for natural gas. A furnace is rated 80,000 Btu/h. What gas flow does it need?
Question 8
Calculation
Use the 45-degree constant 1.414. A stack must jog 16 inches. What is the center-to-center travel between the two 45-degree fittings?
Question 9
Calculation
A 3-story DWV stack is filled with water to the top of a vent 28 ft above the building drain. Use 0.433 psi per foot. What pressure acts on the building drain joints?
Question 10
Calculation
Size a hydromechanical grease interceptor by sink volume. Use these values: a 3-compartment sink, each compartment 18 × 18 × 12 inches; 231 cubic inches per gallon; 75% fill; 1-minute drain time. What flow rate should the interceptor handle?
Question 11
Calculation
Use 0.433 psi per foot. A gravity water tank's water level is 92 ft above a ground-floor fixture. What static pressure does the fixture see?
Question 12
Calculation
A 4-inch building drain runs 66 ft at 1/8 inch per foot. What is the total fall in feet and inches?
Question 13
Calculation
Use the IPC rule that a vent must be at least half the diameter of the drain it serves, never less than 1-1/4 inches. What is the minimum individual vent for a 3-inch water closet drain?
Question 14
Calculation
Use gph = Btu/h input × efficiency ÷ (8.33 × ΔT). A 40,000 Btu/h gas water heater is 80% efficient and raises water 90°F. What is its recovery rate?
Question 15
Calculation
Use 1,000 Btu per cubic foot. A house has a 100,000 Btu/h furnace, a 40,000 Btu/h water heater, a 65,000 Btu/h range and a 35,000 Btu/h dryer. What total gas load must the piping carry?
Question 16
Calculation
Use the 22-1/2-degree constant 2.613. A drain must offset 10 inches with 22-1/2-degree fittings. What is the travel?
Question 17
Calculation
Use 0.433 psi per foot of water. A 5 psi air test equals about how many feet of water head?
Question 18
Calculation
Use these values for an assembly space: occupant load 300, split evenly between men and women; 1 water closet per 75 women required. How many water closets are required for women?
Question 19
Calculation
Use these values: street static pressure 60 psi; elevation of the highest fixture 20 ft (0.433 psi/ft); meter and backflow device losses 12 psi; minimum pressure needed at the fixture 15 psi; developed length 150 ft. What friction loss per 100 ft can the piping use?
Question 20
Calculation
A slope of 1/4 inch per foot is about what percent grade?

Ready for the real exam?

Get every question, unlimited calculation practice and timed mock exams in the app.
Coming soon
Download on the App Store
Coming soon
Get it on Google Play
Not affiliated with any state agency, TDLR, PSI, NFPA, EPA or CSLB. NEC® and National Electrical Code® are registered trademarks of NFPA.
Practice questions are written in our own words and cite code sections by number. Always study from your own copy of the code and the official candidate bulletin.
PrivacyTerms
© 2026 Trovyn Tech LLC