Sanitary drainage: Louisiana Journeyman Plumber Practice Questions
DFU sizing, slope, fittings and changes of direction, cleanouts, sumps and ejectors, backwater valves, indirect waste.
Often missed
Question 1
Under the IPC, what is the minimum slope for a 3-inch horizontal drain?
Correct answer: 1/8 inch per foot
IPC 2021 704.1
The IPC requires 1/4 inch per foot for drains 2-1/2 inches and smaller, 1/8 inch per foot for 3 to 6 inches and 1/16 inch per foot for 8 inches and larger.
Question 2
Under the IPC, what is the minimum slope for a 2-inch horizontal drain?
Correct answer: 1/4 inch per foot
IPC 2021 704.1
Drains 2-1/2 inches and smaller need at least 1/4 inch per foot under the IPC.
Question 3
Under the IPC, what is the minimum slope for an 8-inch building drain?
Correct answer: 1/16 inch per foot
IPC 2021 704.1
Large drains carry enough flow to scour at flatter grades; the IPC allows 1/16 inch per foot for 8 inches and larger.
Question 4
Calculation
A 40-ft horizontal drain is laid at 1/4 inch per foot. How much total fall does it have?
Correct answer: 10.00 inches
Trade practice (slope)
Multiply the slope per foot by the length. Using 1/8 inch per foot by mistake gives 5 inches.
Worked solution
1
Formula
Fall = slope × length
2
Values
Fall = 0.25 in/ft × 40 ft
3
Result
Fall = 10.00 inches
Question 5
Calculation
A 4-inch building drain runs 66 ft at 1/8 inch per foot. What is the total fall in feet and inches?
Correct answer: 0 ft 8.25 in
Trade practice (slope)
One-eighth inch per foot over 66 ft is 8.25 inches. Using 1/4 inch per foot gives 16.5 inches (1 ft 4.5 in).
Worked solution
1
Formula
Fall = 0.125 in/ft × 66 ft = 8.25 in
2
Values
8.25 in is less than 12 in
3
Result
Fall = 0 ft 8.25 in
Question 6
Calculation
A slope of 1/4 inch per foot is about what percent grade?
Correct answer: 2.08%
Trade practice (slope)
A foot is 12 inches, so 1/4 inch per foot is 0.25 ÷ 12, about 2%. Codes often write it as 2 percent.
Worked solution
1
Formula
Percent = rise ÷ run × 100
2
Values
Percent = 0.25 in ÷ 12 in × 100 = 2.083
3
Result
Percent = 2.08%
Question 7
Calculation
The invert of a building drain where it leaves the building is at elevation 96.50 ft. The drain runs 80 ft to the sewer tap at 1/8 inch per foot. What is the invert elevation at the tap?
Correct answer: 95.67 ft
Trade practice (invert elevation)
Convert the fall from inches to feet before subtracting. Subtracting 10 feet instead of 10 inches gives 86.50.
Worked solution
1
Formula
Fall = 0.125 in/ft × 80 ft = 10 in
2
Values
10 in ÷ 12 = 0.833 ft
3
Values
Elevation = 96.50 − 0.833 = 95.667 ft
4
Result
Elevation = 95.67 ft
Question 8
Calculation
A sump pump discharges 15 gpm continuously into a gravity drain. Use the code rule of 2 drainage fixture units per gpm of continuous flow. How many DFU does it add?
Correct answer: 30 DFU
IPC 2021 709.3 / UPC 2021 702.3
Both codes assign 2 DFU for each gallon per minute of continuous or semicontinuous flow, such as pumps and air-conditioning condensate.
Worked solution
1
Formula
DFU = 2 × gpm
2
Values
DFU = 2 × 15
3
Result
DFU = 30 DFU
Question 9
Calculation
Use these values for this problem: lavatory 1 DFU, bathtub 2 DFU, water closet 3 DFU, kitchen sink 2 DFU, clothes washer 3 DFU. A horizontal branch serves 2 lavatories, 1 bathtub and 1 water closet. What is its DFU load?
Correct answer: 7 DFU
IPC 2021 710.1 / UPC 2021 703.2
Add each fixture's DFU, counting both lavatories. Counting one lavatory gives 6.
Worked solution
1
Formula
Lavatories = 2 × 1 = 2
2
Values
Total = 2 + 2 + 3 = 7
3
Result
Load = 7 DFU
Question 10
Calculation
Use these values for this problem: a 2-inch horizontal branch may carry up to 6 DFU, a 2-1/2-inch up to 12 DFU, a 3-inch up to 20 DFU (no more than 2 water closets on 3-inch, for this problem). A branch carries 1 water closet (3 DFU), 2 lavatories (1 each), 1 shower (2) and 1 laundry tray (2). What is the smallest branch size?
Correct answer: 3 inches
IPC 2021 710.1 / UPC 2021 703.2
By DFU alone 2-1/2 inch would carry 9 DFU, but no water closet may discharge into a drain smaller than 3 inches.
Worked solution
1
Formula
DFU = 3 + 2 + 2 + 2 = 9 DFU
2
Values
9 DFU fits 2-1/2 inch by DFU, but a water closet needs at least a 3-inch drain
3
Result
Smallest size = 3 inches
Question 11
Calculation
Use these values for this problem: at 1/4 inch per foot, a building drain of 3 inches carries up to 42 DFU, 4 inches up to 216 DFU and 5 inches up to 480 DFU. A house has 2 bathroom groups at 6 DFU each, a kitchen sink at 2, a dishwasher at 2, a clothes washer at 3 and a laundry tray at 2. What is the smallest building drain allowed?
Correct answer: 3 inches
IPC 2021 710.1 / UPC 2021 703.2
The total of 21 DFU fits within the 3-inch capacity given, and 3 inches also meets the water closet minimum.
Worked solution
1
Formula
DFU = (2 × 6) + 2 + 2 + 3 + 2 = 21 DFU
2
Values
3-inch capacity 42 DFU ≥ 21 DFU
3
Result
Smallest size = 3 inches
Question 12
What is the smallest drain a water closet may discharge into?
Correct answer: 3 inches
IPC 2021 710 / UPC 2021 703
Both codes require at least a 3-inch drain for a water closet.
Question 13
May a horizontal drain be reduced in size in the direction of flow?
Correct answer: No, except for a 4-by-3 water closet bend or flange
IPC 2021 704.2 / UPC 2021 310.5
Reducing a drain downstream creates a choke point that catches solids. The only common exception is the 4 x 3 closet bend or flange.
Question 14
How must a drainage stack compare in size with the horizontal branches connected to it?
Correct answer: Not smaller than the largest branch
IPC 2021 710 / UPC 2021 703
A stack smaller than a branch feeding it would choke. The stack is sized by its total DFU and must be at least as large as the largest branch.
Question 15
A sanitary tee is used to change direction in a drain. In which direction is this allowed?
Correct answer: From horizontal to vertical
IPC 2021 706.3 / UPC 2021 706.2
A sanitary tee turns flow from a horizontal branch down into a vertical stack. It may not turn vertical flow to horizontal or be used flat (horizontal to horizontal).
Get every question, unlimited calculation practice and timed mock exams in the app.
Coming soon
Download on the App Store
Coming soon
Get it on Google Play
Not affiliated with any state agency, TDLR, PSI, NFPA, EPA or CSLB. NEC® and National Electrical Code® are registered trademarks of NFPA.
Practice questions are written in our own words and cite code sections by number. Always study from your own copy of the code and the official candidate bulletin.