Vermont Journeyman Electrician Calculations Practice

Each problem shows the formula, the numbers and every step. The app generates new problems without limit.
Question 1
Calculation
A 120 V source drives 15 A through a resistive load. What is the resistance of the load?
Question 2
41A7,200V?A240VNp =Ns =CorePrimarySecondarySourceLoad
Calculation
An ideal transformer steps 7,200 V down to 240 V. The primary current is 41 A. What is the secondary current?
Question 3
Calculation
A 208 V three-phase feeder carries 65 A over a one-way length of 200 ft using 3 AWG copper conductors (52,620 cmil). Use K = 12.9. What is the voltage drop?
Question 4
Calculation
A single-phase resistive load draws 15 A at 240 V. How many watts does it use?
Question 5
Calculation
A metal box contains 5 insulated 10 AWG conductors, 1 device (switch or receptacle) on a single yoke, 2 equipment grounding conductors and internal cable clamps. The volume allowance for each 10 AWG conductor is 2.5 in³ (given). What is the minimum box volume?
Question 6
Calculation
A three-phase motor load draws 70 A per line at 480 V with a power factor of 0.8. What is the true power in kW?
Question 7
Calculation
A 480 V circuit supplies a resistive load of 14 Ω. What current flows in the circuit?
Question 8
Calculation
What is the full-load secondary line current of a 225 kVA three-phase transformer with a 480 V secondary?
Question 9
Calculation
A 480 V three-phase feeder carries 135 A over a one-way length of 390 ft using 4/0 AWG aluminum conductors (211,600 cmil). Use K = 21.2. What is the voltage drop?
Question 10
Calculation
A single-phase resistive load draws 36 A at 120 V. How many watts does it use?
Question 11
Calculation
A metal box contains 9 insulated 12 AWG conductors, 1 device (switch or receptacle) on a single yoke, 3 equipment grounding conductors and internal cable clamps. The volume allowance for each 12 AWG conductor is 2.25 in³ (given). What is the minimum box volume?
Question 12
Calculation
A 75 kW three-phase load operates at 208 V with a power factor of 0.9. What is the line current?
Question 13
Calculation
Three resistors of 30 Ω, 38 Ω and 14 Ω are connected in series. What is the total resistance?
Question 14
Calculation
A branch circuit supplies 36 A of continuous load and 11 A of noncontinuous load. The overcurrent device is not listed for 100% continuous operation. What is the minimum overcurrent device rating, before rounding up to a standard size?
Question 15
Calculation
A raceway has a total internal area of 1.496 in². Each 10 AWG conductor, including insulation, has an area of 0.0211 in² (both given). With more than two conductors, fill is limited to 40%. What is the maximum number of conductors allowed?
Question 16
Calculation
Three resistors of 44 Ω, 29 Ω and 28 Ω are connected in parallel. What is the total resistance?
Question 17
Calculation
A branch circuit supplies 25 A of continuous load and 30 A of noncontinuous load. The overcurrent device is not listed for 100% continuous operation. What is the minimum overcurrent device rating, before rounding up to a standard size?
Question 18
Calculation
A raceway has a total internal area of 3.356 in². Each 10 AWG conductor, including insulation, has an area of 0.0211 in² (both given). With more than two conductors, fill is limited to 40%. What is the maximum number of conductors allowed?
Question 19
120V8AWG17A140L =ftSourceUngrounded conductorGrounded conductor (neutral)LoadConductorsizeLoadcurrentOne-way lengthVoltage at load = ?
Calculation
A 120 V single-phase circuit carries 17 A over a one-way length of 140 ft using 8 AWG copper conductors (16,510 cmil). Use K = 12.9. What is the voltage drop?
Question 20
120V3AWG48A100L =ftSourceUngrounded conductorGrounded conductor (neutral)LoadConductorsizeLoadcurrentOne-way lengthVoltage at load = ?
Calculation
A 120 V single-phase circuit carries 48 A over a one-way length of 100 ft using 3 AWG aluminum conductors (52,620 cmil). Use K = 21.2. What is the voltage drop?

Ready for the real exam?

Get every question, unlimited calculation practice and timed mock exams in the app.
Coming soon
Download on the App Store
Coming soon
Get it on Google Play
Not affiliated with any state agency, TDLR, PSI, NFPA, EPA or CSLB. NEC® and National Electrical Code® are registered trademarks of NFPA.
Practice questions are written in our own words and cite code sections by number. Always study from your own copy of the code and the official candidate bulletin.
PrivacyTerms
© 2026 Trovyn Tech LLC