SPS 316 changes to the NEC: Wisconsin Journeyman Electrician Practice Questions
Wisconsin's GFCI wording, island receptacles, service and feeder entry limits, outside disconnects, supplemental electrodes, derating, NM cable and private sewage pumps.
Often missed
Question 1
Under Wisconsin's substitute wording for NEC 210.8(A), which dwelling unit receptacles in the listed locations need GFCI protection?
Correct answer: 125 V, single-phase, 15 and 20 A receptacles
SPS 316.210(1)
SPS 316.210(1)(a) substitutes wording for NEC 210.8(A) that limits the dwelling unit GFCI rule to 125-volt, single-phase, 15- and 20-ampere receptacles in the listed locations.
Question 2
Which part of a Wisconsin dwelling's basement does the GFCI requirement cover?
Correct answer: Unfinished areas not intended as habitable rooms
SPS 316.210(1)
SPS 316.210(1)(b) substitutes wording for NEC 210.8(A)(5): GFCI applies in unfinished portions or areas of the basement not intended as habitable rooms.
Question 3
When does Wisconsin require a receptacle at a kitchen island countertop?
Correct answer: When it is at least 24 in. long and 12 in. deep
SPS 316.210(3)
SPS 316.210(3)(a) requires at least one receptacle at each island and peninsular countertop space with a long dimension of 24 in. or more and a short dimension of 12 in. or more; a peninsula is measured from the connected wall.
Question 4
A flat island top has no way to mount a receptacle within 20 in. above it. Where does Wisconsin allow the receptacle?
Correct answer: Up to 12 in. below the top, if the top overhangs 6 in. or less
SPS 316.210(3)
SPS 316.210(3)(b)2. allows receptacles not more than 12 in. below a flat island or peninsula top with no means to mount within 20 in. above, but not where the top extends more than 6 in. beyond its support base.
Question 5
How far into a Wisconsin building may a raceway with service conductors run before reaching the service disconnect?
Correct answer: Not more than 8 ft
SPS 316.230(3)
SPS 316.230(3)(b) adds a rule to NEC 230.70(A): service raceways or cables may not extend more than 8 ft into the building to the service disconnect, measured from where they pass through the outer surface of the exterior (except as NEC 230.6 allows).
Question 6
A Wisconsin service disconnect is installed outside the building it serves. Where must it be?
Correct answer: Within 30 ft of and in sight of the building
SPS 316.230(3)
SPS 316.230(3)(c) requires an outside service disconnecting means to be no more than 30 ft from and within sight of the building or structure it serves (SPS 316.225 sets the same limit for feeder disconnects).
Question 7
The 2023 NEC requires an outdoor emergency disconnect for one- and two-family dwelling services (NEC 230.85). What does SPS 316 do with that rule?
Correct answer: Leaves it out of the Wisconsin code
SPS 316.230(4)
SPS 316.230(4) says the requirements of NEC 230.85 are not included in the Wisconsin code (SPS 316.225(3) does the same for NEC 225.41).
Question 8
Under the Wisconsin substitute for NEC 230.2(B)(2), when may a building have two service drops for the same class of service?
Correct answer: When over 150 ft apart, with no common raceway or connection
SPS 316.230(1)
SPS 316.230(1)(b) allows two or more drops or laterals for the same class of service if located more than 150 ft apart in a straight line and the wiring supplied by each has no common raceway or connection with any other service.
Question 9
A Wisconsin service uses a single ground rod. What does SPS 316 require?
Correct answer: One more electrode, even if the rod reads 25 ohms or less
SPS 316.250(1)
SPS 316.250 omits the exception in NEC 250.53(A)(2) and requires a single rod, pipe or plate electrode to be augmented by one additional electrode of a type in NEC 250.52(A)(4) to (A)(8).
Question 10
A metal raceway is installed in a concrete slab poured on earth in Wisconsin. What else is required?
Correct answer: A supplemental wire-type equipment grounding conductor
SPS 316.250(3)
SPS 316.250(3) requires a metallic raceway in direct contact with earth, in slabs on earth or in exterior below-grade walls to be augmented with a wire-type equipment grounding conductor sized per NEC 250.122; an aluminum one must be insulated.
Question 11
In Wisconsin, when do the adjustment factors of NEC Table 310.15(C)(1) not apply?
Correct answer: To branch circuits supplying an individual dwelling unit
SPS 316.310
SPS 316.310 adds a rule to NEC 310.15(C)(1): the derating factors in the table do not apply to branch circuits supplying an individual dwelling unit.
Question 12
How must the effluent pump of a private onsite wastewater treatment system be supplied in Wisconsin?
Correct answer: From a separate branch circuit supplying no other loads
SPS 316.300(1)
SPS 316.300(1)(a) requires a separate branch circuit for effluent pumps, bars connecting alarm wiring to the pump circuit, and bars a neutral common to the alarm and pump circuits (so no shared multiwire circuit).
Question 13
A single receptacle at a Wisconsin septic pump chamber has the pump plugged into it. Does it need GFCI protection?
Correct answer: Only if the pump or alarm maker recommends or requires it
SPS 316.300(1)
SPS 316.300(1)(b) says a single receptacle at the pump chamber with an alarm or pump connected does not need GFCI protection unless the alarm or pump manufacturer recommends or requires it.
Question 14
Wisconsin adds Exception No. 4 to NEC 300.4(D). Where is the 1¼ in. setback from the framing edge not required?
Correct answer: Within 8 in. of a device, box, splice or termination
SPS 316.300(2)
SPS 316.300(2) adds an exception to NEC 300.4(D): the distance does not need to be kept within 8 in. of a device, junction box, splice or termination point.
Question 15
NM cable enters a panelboard through a short nonflexible raceway sleeve. What length does Wisconsin allow for that raceway?
Correct answer: 12 in. to 10 ft
SPS 316.312
SPS 316.312 substitutes the intro of NEC 312.5(C) Exception No. 1: cables with entirely nonmetallic sheaths may enter through nonflexible raceways not less than 12 in. and not more than 10 ft long, with a fitting at each end to protect the cable.
Get every question, unlimited calculation practice and timed mock exams in the app.
Coming soon
Download on the App Store
Coming soon
Get it on Google Play
Not affiliated with any state agency, TDLR, PSI, NFPA, EPA or CSLB. NEC® and National Electrical Code® are registered trademarks of NFPA.
Practice questions are written in our own words and cite code sections by number. Always study from your own copy of the code and the official candidate bulletin.